Issue:
Do Powerpact H and J thermal magnetic breakers have adjustment dials?
Product Line:
Powerpact H and J
Resolution:
H frame: No, the thermal and magnetic settings are fixed.
J frame: Yes. The thermal setting is fixed, however the magnetic settings is adjustable by a dial that is adjustable from 5 to 10 times the handle amp rating. Panelboard trim must be removed to access the dial.