Issue:
Available I-O points on the standard ATV61/ATV71.
Product Line:
Altivar 61, Altivar 71
Environment:
All
Cause:
Documentation
Resolution:
Below are the Inputs and Outputs that are on board without adding options:
Analog input #1: +/- 10Vdc bipolar input, 1 bits + 1 sign
resolution, 2ms +/- .5ms sample time
Analog input #2: software selectable for 1-10Vdc or x-y mA
x-y selectable from 0-20mA,
11 bits resolution, 2ms +/- .5ms sample time
Analog output #1: software selectable for 1-10Vdc or x-y mA
x-y selectable from 0-20mA,
10 bits resolution, 2ms +/- .5ms sample time
Relay output #1: one NO, one NC
Relay output #2: one NO
6 logic inputs 24Vdc, 2ms +/- .5ms sample time
Multiple function assignment possible
Positive logic (source) or Negative logic
(sink) choice LI6 offers PTC probe
assignment
Power Removal input: 1 input for interlocking function
(run permissive)
RJ45 port Modbus or CANopen (selectable)
Option cards can be added to increase the available I-O and/or communications options.
Available I-O points on the standard ATV61/ATV71.
Product Line:
Altivar 61, Altivar 71
Environment:
All
Cause:
Documentation
Resolution:
Below are the Inputs and Outputs that are on board without adding options:
Analog input #1: +/- 10Vdc bipolar input, 1 bits + 1 sign
resolution, 2ms +/- .5ms sample time
Analog input #2: software selectable for 1-10Vdc or x-y mA
x-y selectable from 0-20mA,
11 bits resolution, 2ms +/- .5ms sample time
Analog output #1: software selectable for 1-10Vdc or x-y mA
x-y selectable from 0-20mA,
10 bits resolution, 2ms +/- .5ms sample time
Relay output #1: one NO, one NC
Relay output #2: one NO
6 logic inputs 24Vdc, 2ms +/- .5ms sample time
Multiple function assignment possible
Positive logic (source) or Negative logic
(sink) choice LI6 offers PTC probe
assignment
Power Removal input: 1 input for interlocking function
(run permissive)
RJ45 port Modbus or CANopen (selectable)
Option cards can be added to increase the available I-O and/or communications options.
Released for:Schneider Electric USA



