What type of cable is used for connecting medium voltage switchgear to transformers?
Issue:
Sizing the cable for a medium voltage  product.

Product Line:
Medium voltage switchgear and transformers

Environment:
Installation

Cause:
N/A

Resolution:
The transformer manufacturer uses either 7.5kV or 15kV insulated non-shielded cable. Either 1 or 2 #2/0 Cables per phase depending on the line current. Since the cable in non-shielded, air clearances are maintained.

Schneider Electric USA

What type of cable is used for connecting medium voltage switchgear to transformers?
Issue:
Sizing the cable for a medium voltage  product.

Product Line:
Medium voltage switchgear and transformers

Environment:
Installation

Cause:
N/A

Resolution:
The transformer manufacturer uses either 7.5kV or 15kV insulated non-shielded cable. Either 1 or 2 #2/0 Cables per phase depending on the line current. Since the cable in non-shielded, air clearances are maintained.

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.