Do the Micrologic trip unit protective relay functions have ANSI certification?
Issue:
Micrologic trip unit protective relay functions characteristics
Product Line:
NEMA AND DEFINITE PURPOSE CONTACTORS AND STARTERS
Environment:
NEMA SolidState overload relays
Resolution:
No. Our advanced protection functions in the Micrologic P/H trip units are not certified to ANSI C37.2 which requires a 30A output that the M6C cannot deliver.
The basic trip unit functions (overload, short circuit, instantaneous & ground fault) were qualified to ANSI C37.17 and C37.50 as part of the NW qualification.