What is the maximum ambient temperature that a transformer can be installed in?

Issue:
Ventilation and cooling is an important issue in the installation and operation of transformers

Product Line:
LV Transformers

Environment:
Applies to all Low Voltage (LV) Transformers by SquareD/Schneider Electric

Cause:
Excessive heat is destructive to transformers

Resolution:
The average ambient temperature for a transformer over a 24 hour period should not exceed 30 degrees Celsius. For instance, if the transformer ambient temperature was 40 deg. C for 12 hours, then the transformer must not exceed 20 deg. C for the remaining 12 hours to average a 30 deg. ambient temperature.

If the average ambient temperature exceeds 30 degrees Celsius, the derating factor is 0.4% reduction of VA for every degree Celsius above 30 degrees Celsius per IEEE C57 12.96. The IEEE formula that is used to derive the 0.4% factor is valid only up to an AVERAGE of 50 degrees Celsius. Also, using transformers above their listed ambient temperature can shorten the life of the transformer. Due to the number of other factors involved, such as loading, frequency of use, and humidity, no data exists on how high ambient temperatures affect the life of a transformer.


Schneider Electric USA

What is the maximum ambient temperature that a transformer can be installed in?

Issue:
Ventilation and cooling is an important issue in the installation and operation of transformers

Product Line:
LV Transformers

Environment:
Applies to all Low Voltage (LV) Transformers by SquareD/Schneider Electric

Cause:
Excessive heat is destructive to transformers

Resolution:
The average ambient temperature for a transformer over a 24 hour period should not exceed 30 degrees Celsius. For instance, if the transformer ambient temperature was 40 deg. C for 12 hours, then the transformer must not exceed 20 deg. C for the remaining 12 hours to average a 30 deg. ambient temperature.

If the average ambient temperature exceeds 30 degrees Celsius, the derating factor is 0.4% reduction of VA for every degree Celsius above 30 degrees Celsius per IEEE C57 12.96. The IEEE formula that is used to derive the 0.4% factor is valid only up to an AVERAGE of 50 degrees Celsius. Also, using transformers above their listed ambient temperature can shorten the life of the transformer. Due to the number of other factors involved, such as loading, frequency of use, and humidity, no data exists on how high ambient temperatures affect the life of a transformer.


 

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.