What are the contact ratings on a RPF2B** relay?
Issue:
Contact rating on RPF2B relay
Product Line:
Relays and Timers
Environment:
Zelio RPF Power Relays
Resolution:
The NO contacts are rated 30 amps and the NC are rated only 3 amps. The NC contacts are designed for signaling purposes. If 2 relays are mounted side-by-side there must be a 13mm gap between them to maintain the 30 amps, otherwise that figure drops to 25 amps. All contacts are also 250 vac/vdc rated.
Contact rating on RPF2B relay
Product Line:
Relays and Timers
Environment:
Zelio RPF Power Relays
Resolution:
The NO contacts are rated 30 amps and the NC are rated only 3 amps. The NC contacts are designed for signaling purposes. If 2 relays are mounted side-by-side there must be a 13mm gap between them to maintain the 30 amps, otherwise that figure drops to 25 amps. All contacts are also 250 vac/vdc rated.