Issue:
Convert main breaker to a shunt trip
Product Line:
NQ Panelboards.
Environment:
Products sold in North America
Resolution:
The main breaker with a shunt trip would require 4 pole spaces, so it is not possible to convert the existing main breaker to a shunt trip version.
One option may be to backfeed a Main Lug Only panel with a shunt tripped EDB breaker, which would take up 4 available pole spaces.
Convert main breaker to a shunt trip
Product Line:
NQ Panelboards.
Environment:
Products sold in North America
Resolution:
The main breaker with a shunt trip would require 4 pole spaces, so it is not possible to convert the existing main breaker to a shunt trip version.
One option may be to backfeed a Main Lug Only panel with a shunt tripped EDB breaker, which would take up 4 available pole spaces.
Released for:Schneider Electric USA
Issue:
Convert main breaker to a shunt trip
Product Line:
NQ Panelboards.
Environment:
Products sold in North America
Resolution:
The main breaker with a shunt trip would require 4 pole spaces, so it is not possible to convert the existing main breaker to a shunt trip version.
One option may be to backfeed a Main Lug Only panel with a shunt tripped EDB breaker, which would take up 4 available pole spaces.
Convert main breaker to a shunt trip
Product Line:
NQ Panelboards.
Environment:
Products sold in North America
Resolution:
The main breaker with a shunt trip would require 4 pole spaces, so it is not possible to convert the existing main breaker to a shunt trip version.
One option may be to backfeed a Main Lug Only panel with a shunt tripped EDB breaker, which would take up 4 available pole spaces.
Released for:Schneider Electric USA