What is the line dip ride through time for the ATV61 and ATV71 drives?

Issue:
What is the line dip ride through time for the ATV61 and ATV71 drives?

Product Line:
Altivar 61 and Altivar 71

Environment:
All

Cause:
Need to know how long the drive will 'ride through' a dip in line power

Resolution:

Maximum running time (without fault) at Under Voltage with Nominal Torque is:

1. 1000 msec. with a voltage 70% of nominal voltage
2. 500msec. with a voltage 40% of nominal voltage

Schneider Electric USA

What is the line dip ride through time for the ATV61 and ATV71 drives?

Issue:
What is the line dip ride through time for the ATV61 and ATV71 drives?

Product Line:
Altivar 61 and Altivar 71 

Environment:
All

Cause:
Need to know how long the drive will 'ride through' a dip in line power

Resolution:

Maximum running time (without fault) at Under Voltage with Nominal Torque is:

1. 1000 msec. with a voltage 70% of nominal voltage
 
2. 500msec. with a voltage 40% of nominal voltage

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.