What is the torque for installing the lugs into a energy efficient transformer?
Issue:
Torque required to install the lugs into an Energy Efficient Transformer
Product Line:
Environment:
Products sold and used in the United States
Cause:
Installation / Setup
Resolution:
Bolt size Torque (lb-in)
1/4 in 75
5/16 in 135
3/8 in 230
7/16 in 360
1/2 in 480
Torque required to install the lugs into an Energy Efficient Transformer
Product Line:
Environment:
Products sold and used in the United States
Cause:
Installation / Setup
Resolution:
Bolt size Torque (lb-in)
1/4 in 75
5/16 in 135
3/8 in 230
7/16 in 360
1/2 in 480
Released for:Schneider Electric USA