What are the Standard Voltage Codes for NEMA Contractors and Starters?
Issue:
Information on the common coil voltage codes for the NEMA Type S Contactors and starters
Product Line:
Contractors and Starters
Environment:
NEMA Type S
Resolution:
Voltages
60/50 HZ
24 Vac - V 01 (Must include Form S (Separate control) where 24 V coil is available on NEMA Starter 00-3 not available on NEMA 4-7)
120/110 Vac - V 02 Must include Form S (Separate control) on poly phase devices
208 Vac - V 08
240/220 Vac - V 03
480/440 Vac - V 06
600/550 Vac - V 07
Specify V 99 For non-standard voltages. Check for availability.
Information on the common coil voltage codes for the NEMA Type S Contactors and starters
Product Line:
Contractors and Starters
Environment:
NEMA Type S
Resolution:
Voltages
60/50 HZ
24 Vac - V 01 (Must include Form S (Separate control) where 24 V coil is available on NEMA Starter 00-3 not available on NEMA 4-7)
120/110 Vac - V 02 Must include Form S (Separate control) on poly phase devices
208 Vac - V 08
240/220 Vac - V 03
480/440 Vac - V 06
600/550 Vac - V 07
Specify V 99 For non-standard voltages. Check for availability.
Released for:Schneider Electric USA