Can a 3-phase QO load center be used on a 240 V "high leg" system?

Article available in these languages: Spanish

Issue:
Application

Product Line:
QO Load Center

Resolution:
Yes, but it is important to understand some limitations. This "high leg" delta system referred to is actually a 3 phase, 4 wire, 240/120 V delta system. It has a number of common names, including high leg, wild leg, stinger leg, etc. This system provides 240 V phase-phase power between all 3 phases, plus 120 V phase-neutral power on 2 of the 3 phases. The problem, however, is with the phase-neutral on the 3rd phase: it measures 208 V, which is not a usable downstream voltage since it is too high. This is what gives the system its nickname, high leg. This high leg is commonly the B phase, but could be the A or C phase.
Selecting QO breakers for this system must be done carefully. Here are some guidelines:

1-pole QO Breakers
  • Standard 1-pole QO breakers have a voltage rating of either 120/240 V (e.g., QO120) or just 120 V (e.g. QO120GFI). These should only be applied on phases measuring 120 V phase to neutral, never on the phase measuring 208 V phase to neutral.

2-pole QO Breakers
  • Standard 2-pole QO breakers have a voltage rating of 120/240V (e.g., QO240). These should only be applied on phases measuring 120 V phase to neutral, never on the phase measuring 208 V phase to neutral.
  • Special 2-pole QO breakers with "H" suffix have a voltage rating of 240 V (e.g., QO240H). These may be applied on any of the phases, including the high leg phase.

3-pole QO Breakers
  • Standard 3-pole QO breakers have a voltage rating of 240 V (e.g., QO330). These may be applied on any of the phases, including the high leg phase.

NOTE: The installer should be careful to follow NEC and/or local electrical codes regarding the wiring, marking, and usage of this system.

Schneider Electric USA

Can a 3-phase QO load center be used on a 240 V "high leg" system?

Article available in these languages: Spanish

Issue:
Application

Product Line:
QO Load Center

Resolution:
Yes, but it is important to understand some limitations. This "high leg" delta system referred to is actually a 3 phase, 4 wire, 240/120 V delta system. It has a number of common names, including high leg, wild leg, stinger leg, etc. This system provides 240 V phase-phase power between all 3 phases, plus 120 V phase-neutral power on 2 of the 3 phases. The problem, however, is with the phase-neutral on the 3rd phase: it measures 208 V, which is not a usable downstream voltage since it is too high. This is what gives the system its nickname, high leg. This high leg is commonly the B phase, but could be the A or C phase.
Selecting QO breakers for this system must be done carefully. Here are some guidelines:

1-pole QO Breakers
  • Standard 1-pole QO breakers have a voltage rating of either 120/240 V (e.g., QO120) or just 120 V (e.g. QO120GFI). These should only be applied on phases measuring 120 V phase to neutral, never on the phase measuring 208 V phase to neutral.

2-pole QO Breakers
  • Standard 2-pole QO breakers have a voltage rating of 120/240V (e.g., QO240). These should only be applied on phases measuring 120 V phase to neutral, never on the phase measuring 208 V phase to neutral.
  • Special 2-pole QO breakers with "H" suffix have a voltage rating of 240 V (e.g., QO240H). These may be applied on any of the phases, including the high leg phase.

3-pole QO Breakers
  • Standard 3-pole QO breakers have a voltage rating of 240 V (e.g., QO330). These may be applied on any of the phases, including the high leg phase.

NOTE: The installer should be careful to follow NEC and/or local electrical codes regarding the wiring, marking, and usage of this system.

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.