{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.

How can we help you today?

Why will the KC breakers not fit into the HCM interior?

Issue:
HCM interior cannot take KC circuit breakers

Product Line:
Panelboard, Circuit Breakers

Environment:
ILine Panelboard and Circuit Breakers

Resolution:
Size wise the KC will fit. However, the KC breaker needs a vented trim to allow the gases to escape on a high level fault. The HCM trim is not vented. But the Powerpact JJ and JL do not need the vented trim so they can be used.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: