What is the lug torque specification for a Powerpact J frame circuit breaker?
Product Line:
Circuit Breakers

Resolution:
The standard Al/Cu lugs are rated at 225 lb-in and require a 5/16 in hex bit torque wrench. See below for lug information.
The AL175JD (150 - 175 A) is 225 lb - in.
The AL250JD (200 - 250 A) is 225 lb - in.
The CU250JD (150 - 250 A) is 250 lb - in

See instruction bulletin, 48940-221-02

Schneider Electric USA

What is the lug torque specification for a Powerpact J frame circuit breaker?
Product Line:
Circuit Breakers

Resolution:
The standard Al/Cu lugs are rated at 225 lb-in and require a 5/16 in hex bit torque wrench. See below for lug information.
The AL175JD (150 - 175 A) is 225 lb - in.
The AL250JD (200 - 250 A) is 225 lb - in.
The CU250JD (150 - 250 A) is 250 lb - in

See instruction bulletin, 48940-221-02

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.