Can comb bus bars for Multi 9 C60BP circuit breakers be cut to any desired length?
Issue:
Cutting M9 UL recognized comb busbars for C60BP circuit breakers
Product Line:
UL 489 listed Multi 9
Environment:
Installation
Resolution:
IEC style comb bus bars are cuttable. Use end caps M9XCEC10 on both ends.
Cutting M9 UL recognized comb busbars for C60BP circuit breakers
Product Line:
UL 489 listed Multi 9
Environment:
Installation
Resolution:
- "Standard" UL recognized busbars cannot be cut, but there are two lengths to choose from. For unused positions - use end cap M9XCTC18.
- M9XUP106 M9XUP312 M9XUP312 M9XUP312 M9XUP312 M9R81425
- "Cuttable" UL recognized busbars are also available. For unused positions use end cap M9XCEC10.
- M9XCP157 M9XCP256 M9XCP357 M9XCA137 M9XCA348
IEC style comb bus bars are cuttable. Use end caps M9XCEC10 on both ends.
Released for:Schneider Electric USA