Will the 240 Vac Coil for an 8501 Type K Relay Work if Supplied with 208 Vac?
Issue:
208 VAC coil option for a general purpose miniature relay
Product Line:
General Purpose Relays
Environment:
Class 8501 Type K relays
Resolution:
Yes. The 240 Vac Coil for 8501 Type K relays has an operating limit of 192 to 264 Vac.
208 VAC coil option for a general purpose miniature relay
Product Line:
General Purpose Relays
Environment:
Class 8501 Type K relays
Resolution:
Yes. The 240 Vac Coil for 8501 Type K relays has an operating limit of 192 to 264 Vac.
Released for:Schneider Electric USA