Issue:
Torque value for a 42 circuit 400 amp NQ Main lug panel
Product Line:
Panelboards.
Environment:
Products sold in the United States.
Cause:
Maintenance.
Resolution:
Lug can accept (1) 1/0-750 kcmil conductor, or (2) 1/0-350 kcmil which needs to be torqued to 275-300 in lbs.