Issue:
Product features
Product Line:
Load Center Ground Bars
Resolution:
The terminals provided on the PK3GTA1 through PK27GTA ground bars will accept the following:
NOTES:
1) The ground bars will accept either solid or stranded type wires.
2) As shown below the PK__GTA ground bars will accept Multiple wires for certain sizes.
3) ONLY the PK27GTA comes standard with one lug that mounts to the TOP of the ground bar and will accept (1) #6 - 2/0 Cu/Al wire
Wire Sizes for ALL the PK3GTA1 through PK27GTA ground bars:
(1) #14 - #4 CU / AL
(2 or 3) #14 CU wires
(2 or 3) # 12 CU / AL wires
(2 or 3) #10 CU / AL wires
Torque requirements:
Wire range Torque LB-IN
(1) #4 CU / AL 35
(1) #6 CU / AL 35
(1) #8 CU / AL 25
(1) #10 - 14 CU, #10 - 12 AL 20
(2 or 3) #14 CU 25
(2 or 3) #12 CU / AL 25
(2 or 3) #10 AL 25
SEE THE ATTACHMENT FOR THE DIMENSIONAL INFORMATION FOR THE GROUND BARS.
Released for:Schneider Electric USA
Issue:
Product features
Product Line:
Load Center Ground Bars
Resolution:
The terminals provided on the PK3GTA1 through PK27GTA ground bars will accept the following:
NOTES:
1) The ground bars will accept either solid or stranded type wires.
2) As shown below the PK__GTA ground bars will accept Multiple wires for certain sizes.
3) ONLY the PK27GTA comes standard with one lug that mounts to the TOP of the ground bar and will accept (1) #6 - 2/0 Cu/Al wire
Wire Sizes for ALL the PK3GTA1 through PK27GTA ground bars:
(1) #14 - #4 CU / AL
(2 or 3) #14 CU wires
(2 or 3) # 12 CU / AL wires
(2 or 3) #10 CU / AL wires
Torque requirements:
Wire range Torque LB-IN
(1) #4 CU / AL 35
(1) #6 CU / AL 35
(1) #8 CU / AL 25
(1) #10 - 14 CU, #10 - 12 AL 20
(2 or 3) #14 CU 25
(2 or 3) #12 CU / AL 25
(2 or 3) #10 AL 25
SEE THE ATTACHMENT FOR THE DIMENSIONAL INFORMATION FOR THE GROUND BARS.
Released for:Schneider Electric USA