What are the available rating plugs and settings for the UL listed/ANSI certified Masterpact NT/NW universal power circuit breakers?
Issue:
What are the Catalog numbers of the Rating plugs for NT/NW Masterpact breakers?
 
Product Line:
Circuit Breakers
 
Resolution:
Interchangeable rating plugs are available to limit the long time threshold setting range for greater versatility (all numbers represent multipliers of the In sensor rating of the breaker).
UL Listed/ANSI Certified
Type A: 0.4, 0.45, 0.5, 0.6, 0.625, 0.7, 0.8, 0.9, 1
Type B: 0.4, 0.44, 0.5, 0.58, 0.625, 0.75, 0.88, 0.95, 1
Type C: 0.417, 0.50, 0.533, 0.583, 0.667, 0.75, 0.933, 0.95, 1
Type D: 0.4, 0.48, 0.64, 0.7, 0.8, 0.9, 0.93, 0.95, 1
Type E: 0.6, 0.7, 0.75, 0.8, 0.85, 0.9, 0.93, 0.95, 1
Type F: 0.84, 0.86, 0.88, 0.9, 0.92, 0.94, 0.96, 0.98, 1
Type G: 0.66, 0.68, 0.7, 0.72, 0.74, 0.76, 0.78, 0.8, 0.82
Type H: 0.48, 0.5, 0.52, 0.54, 0.56, 0.58, 0.6, 0.62, 0.64

Rating plug table

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.