Issue:
Short Circuit Current rating (SCCR) for the 8536 starters
Product Line:
Nema and Definite Purpose and Starters
Environment:
North American Products
Cause:
Needs the short current circuit rating (SCCR) for the 8536 starters.
Resolution:
The following interrupting ratings have been established by UL and will apply to the starter only. Horsepower ratings are 480v 3phase.
Short Circuit Current rating (SCCR) for the 8536 starters
Product Line:
Nema and Definite Purpose and Starters
Environment:
North American Products
Cause:
Needs the short current circuit rating (SCCR) for the 8536 starters.
Resolution:
The following interrupting ratings have been established by UL and will apply to the starter only. Horsepower ratings are 480v 3phase.
Horsepower | SCCR(A) |
>1 thru 50 | 5,000 |
51 thru 200 | 10,000 |
201 thru 400 | 18,000 |
401 thru 600 | 30,000 |
Released for:Schneider Electric USA
Issue:
Short Circuit Current rating (SCCR) for the 8536 starters
Product Line:
Nema and Definite Purpose and Starters
Environment:
North American Products
Cause:
Needs the short current circuit rating (SCCR) for the 8536 starters.
Resolution:
The following interrupting ratings have been established by UL and will apply to the starter only. Horsepower ratings are 480v 3phase.
Short Circuit Current rating (SCCR) for the 8536 starters
Product Line:
Nema and Definite Purpose and Starters
Environment:
North American Products
Cause:
Needs the short current circuit rating (SCCR) for the 8536 starters.
Resolution:
The following interrupting ratings have been established by UL and will apply to the starter only. Horsepower ratings are 480v 3phase.
Horsepower | SCCR(A) |
>1 thru 50 | 5,000 |
51 thru 200 | 10,000 |
201 thru 400 | 18,000 |
401 thru 600 | 30,000 |
Released for:Schneider Electric USA