What is the mechanical interlock for (2) LC1F400 contactors?
Issue:
What is the mechanical interlock to build an LC1F400 as a reversing unit?
Product Line:
IEC Contactors and Starters
Environment:
Tesys F Contactors
Cause:
LC1F Contactors are not available as reversing units
Resolution:
For horizontal mounting, use an LA9FJ970 mechanical interlock and an LA9FJ976 kit of 3 power connectors. For vertical mounting, use an LA9FJ4J mechanical interlock. There are no power connectors offered with vertical mounting.
What is the mechanical interlock to build an LC1F400 as a reversing unit?
Product Line:
IEC Contactors and Starters
Environment:
Tesys F Contactors
Cause:
LC1F Contactors are not available as reversing units
Resolution:
For horizontal mounting, use an LA9FJ970 mechanical interlock and an LA9FJ976 kit of 3 power connectors. For vertical mounting, use an LA9FJ4J mechanical interlock. There are no power connectors offered with vertical mounting.
Released for:Schneider Electric USA