Does it matter where you put the SDSA1175 or SDSA1175T in the panel?
Issue:
Location of SDSA1175/SDSA1175T in the panel
Product Line:
Surge Protection.
Environment:
Products sold in the United States.
Cause:
Assembly, Installation.
Resolution:
To enhance the performance of the SDSA1175/SDSA1175T, twist and keep the conductor length as short as possible by trimming down the wires (do not loop or coil the wires and avoid sharp bends). Always connect the SDSA to the circuit breaker(s) found in the closest proximity. Increasing the SDSA conductor length will degrade its performance.
Location of SDSA1175/SDSA1175T in the panel
Product Line:
Surge Protection.
Environment:
Products sold in the United States.
Cause:
Assembly, Installation.
Resolution:
To enhance the performance of the SDSA1175/SDSA1175T, twist and keep the conductor length as short as possible by trimming down the wires (do not loop or coil the wires and avoid sharp bends). Always connect the SDSA to the circuit breaker(s) found in the closest proximity. Increasing the SDSA conductor length will degrade its performance.