What are the torque requirements for QO circuit breakers' wire binding screws and clamp plates?
Issue:
Torque requirements for QO and QOB breakers' wire binding screws and clamp plates

Product Line:
Circuit Breakers

Resolution:
The following table shows the torque value requirements for the wire binding screws and clamp plates of QO and QOB circuit breakers:
QO breaker binding screw torque summary
TypeDescriptionTorque lb-in (N-m)
QO/QOB10 - 30 A, 1, 2, and 3 pole36 (4)
QO/QOB35 - 70 A, 1 and 2 pole and 40 - 60 A, 3 pole 45 (5)
QO/QOB-VH, QOH40 - 125 A, 2 pole50 (5.6)
QO/QOB-VH,40 - 100 A, 3 pole50 (5.6)
QO/QOB70 - 100 A, 3 pole50 (5.6)
QO/QOB-H40 - 100 A, 2 pole50 (5.6)
QO/QOB,80 - 125 A, 2 pole50 (5.6)
QO/QO-VH150 - 200 A, 2 pole250 (28.3)
QOB-VH150 A, 2 and 3 pole250 (28.3)
QO Tandem(Ex: QO2020, QOT1515...)25 (2.8)

Schneider Electric USA

What are the torque requirements for QO circuit breakers' wire binding screws and clamp plates?
Issue:
Torque requirements for QO and QOB breakers' wire binding screws and clamp plates

Product Line:
Circuit Breakers

Resolution:
The following table shows the torque value requirements for the wire binding screws and clamp plates of QO and QOB circuit breakers:
 
QO breaker binding screw torque summary
TypeDescriptionTorque lb-in (N-m)
QO/QOB10 - 30 A, 1, 2, and 3 pole36 (4)
QO/QOB35 - 70 A, 1 and 2 pole and 40 - 60 A, 3 pole 45 (5)
QO/QOB-VH, QOH40 - 125 A, 2 pole50 (5.6)
QO/QOB-VH,40 - 100 A, 3 pole50 (5.6)
QO/QOB70 - 100 A, 3 pole50 (5.6)
QO/QOB-H40 - 100 A, 2 pole50 (5.6)
QO/QOB,80 - 125 A, 2 pole50 (5.6)
QO/QO-VH150 - 200 A, 2 pole250 (28.3)
QOB-VH150 A, 2 and 3 pole250 (28.3)
QO Tandem(Ex: QO2020, QOT1515...)25 (2.8)

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.