What is the replacement for a PKA36125G?
Issue:
PKA36125G obsolescence
Product Line:
Busway Circuit Protection
Environment:
Breaker installation
Resolution:
Depending on the system voltage and the required short circuit rating, it could be a PHG36125G or a PHJ36125G.
AIC Rating (in amps):
PKA36125G obsolescence
Product Line:
Busway Circuit Protection
Environment:
Breaker installation
Resolution:
Depending on the system voltage and the required short circuit rating, it could be a PHG36125G or a PHJ36125G.
AIC Rating (in amps):
Model | 240VAC | 480VAC | 600VAC |
PHG | 65k | 35k | 18k |
PHJ | 100k | 65k | 25k |