Issue:
Is special cable needed for MV surge protective devices when connecting to MV gear ?
Product Line:
Meduim Voltage SPD
Environment:
MV Switchgear
Cause:
Clarification
Resolution:
The Cable to connect to the phases is #4- 7 strand 5kV cable. P/N is 1390-000820.
Cable to ground is #4- 7 strand bare cable. P/N is 1342-004003.