If an EVlink charging station is in use charging a vehicle and there is a power interruption, will the charger allow the battery voltage to back feed onto the utility grid?
Issue:
Power lost to EVlink charging station.
Product Line:
PTEVC - Electric Vehicle Systems
Environment:
Installed chargers during operation
Cause:
Power loss to station
Resolution:
No, it will not. A contactor in the charging station will open when the power is lost. It will not close again until the utility power is restored and the vehicle requests charge.
Power lost to EVlink charging station.
Product Line:
PTEVC - Electric Vehicle Systems
Environment:
Installed chargers during operation
Cause:
Power loss to station
Resolution:
No, it will not. A contactor in the charging station will open when the power is lost. It will not close again until the utility power is restored and the vehicle requests charge.
Released for:Schneider Electric USA