{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
What Loud noise or squealing is coming from legacy Airflow unit ?
Issue:
This document describes what to look for in an legacy airflow unit if you discover a loud noise or squealing noise.

Product line:
Airflow, AFX, CCT, CM, TC.

Environment:
All Product models, all serial numbers.

Cause:
Possible fan or motor bearing noise.

Resolution:
Loud noises or squealing coming from unit is usually indicative of a fan issue.
  • Bearings need to be check for proper lubrication.
  • Blower wheel and housing need to be checked for alignment.
  • Fan belt and motor pulley. Check for worn belt or dirty and grease on the pulley.
  • Check for cracks in the motor adjustment plate.
  • Ensure that the motor is secure to the motor adjustment plate.
  • Verify motor amperage to the nameplate (overheating).
  • NOTE: most bearings are a sealed cartridge style which need to be replaced, pillow block bearings should be greased accordingly.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: