What can cause an OL1 fault on the ATV21 or ATV212 drives?
Issue:
OL1 fault on ATV21/ATV212 drives.

Product line:
Altivar ATV212, ATV21

Environment:
All models, all serial numbers

Cause:
OL1 is a drive overload fault.  The motor is pulling to many amps and the internal overload is tripping.

Resolution:

OL1 is an overload fault.
tHr parameter under main menu AUF is what determines the overload settings for a motor.  It is normally programmed to match motor FLA.
Confirm that the motor settings including uL, F415 and F417 match your motor name plate.
Check ACC time and make sure it is not too short a ramp up time.
Set AU1 to 0.
Measure current draw by motor, if possible, at the output to the motor.  If the current draw surpasses tHr value, then it will eventually fault out on OL1, given enough time has passed.
Check for power drop in the line side of the drive.
Can also try setting PT to 0.


Schneider Electric USA

Attachment(s)
ATV212_programming_manual_EN_S1A53838_03.pdf [3.52 MB]
What can cause an OL1 fault on the ATV21 or ATV212 drives?
Issue: 
OL1 fault on ATV21/ATV212 drives.

Product line:
Altivar ATV212, ATV21 

Environment:
All models, all serial numbers 

Cause:
OL1 is a drive overload fault.  The motor is pulling to many amps and the internal overload is tripping.

Resolution:

OL1 is an overload fault.
tHr parameter under main menu AUF is what determines the overload settings for a motor.  It is normally programmed to match motor FLA.
Confirm that the motor settings including uL, F415 and F417 match your motor name plate.
Check ACC time and make sure it is not too short a ramp up time.  
Set AU1 to 0.
Measure current draw by motor, if possible, at the output to the motor.  If the current draw surpasses tHr value, then it will eventually fault out on OL1, given enough time has passed.
Check for power drop in the line side of the drive.
Can also try setting PT to 0.


 

Schneider Electric USA

Attachment(s)
ATV212_programming_manual_EN_S1A53838_03.pdf [3.52 MB]
Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.