Secondary injection testing vs. primary injection testing for circuit breakers
Issue:
Secondary injection testing vs. primary injection testing for circuit breakers

Product Line:
Molded Case Circuit Breakers

Resolution:
Secondary injection testing:
  • Can be done on electronic breakers only
  • Quick
  • Tests the trip unit only
  • Easier
  • Takes less expertise to run the test
  • Test kit is small and portable
  • Less expensive
Primary injection testing:
  • Can be done on thermal magnetic and electronic breakers
  • Time intensive
  • Tests complete breaker from the CT, CT wiring to the trip unit, and the trip unit
  • Takes more expertise to run the test
  • Equipment is heavy and less portable
  • More expensive

Schneider Electric USA

Secondary injection testing vs. primary injection testing for circuit breakers
Issue:
Secondary injection testing vs. primary injection testing for circuit breakers

Product Line:
Molded Case Circuit Breakers

Resolution:
Secondary injection testing:
  • Can be done on electronic breakers only
  • Quick
  • Tests the trip unit only
  • Easier
  • Takes less expertise to run the test
  • Test kit is small and portable
  • Less expensive
Primary injection testing:
  • Can be done on thermal magnetic and electronic breakers
  • Time intensive
  • Tests complete breaker from the CT, CT wiring to the trip unit, and the trip unit
  • Takes more expertise to run the test
  • Equipment is heavy and less portable
  • More expensive

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.