Search FAQs
Video: How do I set a PowerPact or Masterpact circuit breaker with a Micrologic trip unit to a different specified amperage?
Issue:
How to adjust PowerPact P or R or Masterpact circuit breakers with Micrologic trip units to a different Amp rating?
Product Line:
PowerPact P, PowerPact R, Masterpact NW, Masterpact NT
Resolution:
The attached spreadsheet gives you the sensor plug and Long Time (rating plug) settings that will set the breaker to any amperage within its range.
Note that many amp settings can be attained with more than one rating plug and sensor combination.
Sensor plugs can be changed to a lower amperage in some cases; they cannot be increased from the original size, but they can be reduced as much as 50%.
It is not possible to put a 100A or 250A sensor in a 400A or larger breaker. 400A and larger breakers cannot accept 100A or 250A sensors.
See circuit breaker section of the digest for a chart showing possible sensor plugs for breakers 3200A and under.
Sensor Plug Replacement Guide attached includes references for amperages above 3200A.
How to adjust PowerPact P or R or Masterpact circuit breakers with Micrologic trip units to a different Amp rating?
Product Line:
PowerPact P, PowerPact R, Masterpact NW, Masterpact NT
Resolution:
The attached spreadsheet gives you the sensor plug and Long Time (rating plug) settings that will set the breaker to any amperage within its range.
Note that many amp settings can be attained with more than one rating plug and sensor combination.
Sensor plugs can be changed to a lower amperage in some cases; they cannot be increased from the original size, but they can be reduced as much as 50%.
It is not possible to put a 100A or 250A sensor in a 400A or larger breaker. 400A and larger breakers cannot accept 100A or 250A sensors.
See circuit breaker section of the digest for a chart showing possible sensor plugs for breakers 3200A and under.
Sensor Plug Replacement Guide attached includes references for amperages above 3200A.
Released for:Schneider Electric USA
Attachment(s)
Explore more
Range:
Explore more
Range: