Fault F49 on an XW6848?

Issue:
F49 fault on an XW6848

Product Line:
XW6048, XW4548, XW4024, XW6848+, XW5548+

Environment:
Applications that use the XW or XW+ series inverter/chargers

Cause:
Inverter faults with F49

Resolution:
The F49 is a DC over voltage, this will occur if the battery exceeds(35 VDC) for a 24 Volts and (70 VDC) for a 48 volt system.  This fault will also occur if the batteries are disconnected while the inverter is operating or if the high battery cut out is set too low.

You can clear the fault and make sure batteries are properly connected as well as setting the HBCO to a value that the battery will not exceed.
 

 

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.