How can we help you today?
Video: Disabling Ethernet Network Connectivity on TeSys T Motor Management System
Issue:
How to disable Ethernet Network connectivity in Tesys T controllers?
Product Line:
IEC Contactors and Overload relays
Environment:
Tesys T motor management system
Resolution:
There is no setting in the software to disable the ethernet network. On the Tesys T you actually use hardware to disable the network. There are two dials on the face of the device, a Tens dial and a Ones dial. On the Ones dial, choose the Disabled setting and then power cycle the Tesys T. The device will no longer look for a network and will not give the Network settings warning.
How to disable Ethernet Network connectivity in Tesys T controllers?
Product Line:
IEC Contactors and Overload relays
Environment:
Tesys T motor management system
Resolution:
There is no setting in the software to disable the ethernet network. On the Tesys T you actually use hardware to disable the network. There are two dials on the face of the device, a Tens dial and a Ones dial. On the Ones dial, choose the Disabled setting and then power cycle the Tesys T. The device will no longer look for a network and will not give the Network settings warning.
Released for:Schneider Electric USA
Explore more
Range:
Explore more
Range: