Are CAFI or AFI Arc-Fault circuit breakers available for NF Panelboards?
Issue:
For NF panelboards, does Schneider Electric offer arc-fault branch circuit breakers?

Product Line:
EDB, EGB, EJB breakers for NF Panelboards

Environment:
Products sold in North America

Resolution:
Arc-fault circuit breakers are not available for NF panelboards.

The requirement for Arc-Fault Circuit-Interrupter Protection is outlined in Article 210.12 of the National Electric Code (NFPA-70, 2011 Edition), and is for 120V, 15 and 20A branch circuits, in dwelling units. 120V is the phase to neutral voltage, and can be found in 120/240V 1-phase/3-wire, and 208Y/120V 3-phase/4-wire systems. At these voltages, type NQ panelboards should be used, with QO(B) arc-fault circuit breakers. QO(B) breaker are not for use in NF Panelboards.

NF panelboards, and their respective EDB/EGB/EJB circuit breakers, are designed and listed to be used at the higher voltage of 480Y/277V. While electrical codes can change, currently there is no requirement for arc-fault circuit breakers at 277V. Therefore, arc-fault breakers are not available for NF Panelboards.

In summary, if arc-fault breakers are required in a Panelboard, assuming the system has 120V phase to neutral, choose type NQ Panelboards and QO(B) arc-fault breakers.

Schneider Electric USA

Are CAFI or AFI Arc-Fault circuit breakers available for NF Panelboards?
Issue:
For NF panelboards, does Schneider Electric offer arc-fault branch circuit breakers?

Product Line:
EDB, EGB, EJB breakers for NF Panelboards

Environment:
Products sold in North America

Resolution:
Arc-fault circuit breakers are not available for NF panelboards.

The requirement for Arc-Fault Circuit-Interrupter Protection is outlined in Article 210.12 of the National Electric Code (NFPA-70, 2011 Edition), and is for 120V, 15 and 20A branch circuits, in dwelling units. 120V is the phase to neutral voltage, and can be found in 120/240V 1-phase/3-wire, and 208Y/120V 3-phase/4-wire systems. At these voltages, type NQ panelboards should be used, with QO(B) arc-fault circuit breakers. QO(B) breaker are not for use in NF Panelboards.

NF panelboards, and their respective EDB/EGB/EJB circuit breakers, are designed and listed to be used at the higher voltage of 480Y/277V. While electrical codes can change, currently there is no requirement for arc-fault circuit breakers at 277V. Therefore, arc-fault breakers are not available for NF Panelboards.

In summary, if arc-fault breakers are required in a Panelboard, assuming the system has 120V phase to neutral, choose type NQ Panelboards and QO(B) arc-fault breakers.

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.