Product Line
CSH30
Resolution
Withstanding characteristics of CSH30 are:
Continuous overload : 300 A primary
1 second overload : 12.5kA primary
Limiting dynamic value : 32kA peak (one time)
Within these limits Sepam will continue to work properly.
Released for:Schneider Electric USA

