{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
What does the different colors mean in the SCI file?

There are three colors associated with different elements in an SCL file.
1. Black
a. The element properties may be modified
2. Gray
a. The element properties may not be modified.
3. Red
a. The element has an error status.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.