{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
Why does the Quantum Unity PLC (140CPU43412A) timer reset on a power cycle?

The timer resets on a power cycle because the customer has made a Project Backup. When a Project backup is made, every power cycle
will cause a cold restart (%S0). This cold restart will reset all timers.


Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: