%QX3.0 ~ %QX3.3 outputs are out of control and a TM5PCDPS Profibus module is used.
Please put %QX2.0 ~ %QX2.7 and %QX3.0 ~ %QX3.3 of DO12TE module in different POUs and different tasks. Otherwise, %QX3.0 ~ %QX3.3 will be out of control when some of %QX2.0 ~ %QX2.7 are used in same task.
Released for:Schneider Electric USA



