{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
Wiring a 2-wire Transmitter to an STBACI1400 Analog Input

Issue
This resolution describes how to wire 2-wire analog transmitters to the inputs of an STBACI1400 analog input module.


Product Line
Advantys STB
STBACI1400


Environment


Resolution
2-wire analog transmitters require a loop power supply to power the loop. The following diagram shows how this is done with a single power supply for all current loops.


Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: