{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
Step by step process to change the units in the REG48 and REG96 from Deg. C to Deg. F.

Goals and Symptoms

Step by step process to change the units in the REG48 and REG96 from Deg. C to Deg. F.

Facts and Changes

REG48
REG96
°C
°F

Causes and Fixes

Originaly, the parameter to change the temperature units is not accesible from the front face.
So first, you have to allow the display of this parameter.
Steps to follow:
Press the key SEL until you display "Ch 1".
Press "Down" arrow key until you display "Ch12" , "dSP".
Press SEL
Press "Down" arrow key until you display "dP17".
Press SEL
Change the value from FEB0 to FEA0 with the "Down" arrow key.
Press SEL
Press A/M key to exit.

Now you can have access to the unit parameter.
Steps to follow:
Press the key SEL until you display "Ch 1".
Press "Down" arrow key until you display "Ch 6".
Press SEL
Press "Down" arrow key until you display "PvU"
Press SEL
Change the value from °C to °F with the arrow key.
Press SEL
Press A/M key to exit.


Legacy KB System (APS) Data: RESL201914 V1.0, Originally authored by LaBe on 04/06/2010, Last Edited by LaBe on 04/06/2010
Related ranges: Zelio Control

Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: