{}

Our Brands

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
What does the 'Modbus Exception Code 03 Illegal Data Value' error mean when writing to a External Modbus Control Register on a 7650?

Product Line
ION7650/7550

Environment
Register Writing

Resolution
The meter is locked into a Read-Only mode when the password security is anything other than the default of 0 (zero).  To write to an External Modbus control registers requires password security to either be disabled, or set to 0.

Schneider Electric USA

What does the 'Modbus Exception Code 03 Illegal Data Value' error mean when writing to a External Modbus Control Register on a 7650?

Product Line
ION7650/7550

Environment
Register Writing

Resolution
The meter is locked into a Read-Only mode when the password security is anything other than the default of 0 (zero).  To write to an External Modbus control registers requires password security to either be disabled, or set to 0.

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.