How to connect 3-Wire Modbus to an ION Meter

The Shield and GND (ground) connections are internally connected in an ION meter using a diode bridge.
Wiring diagram

This is the best wiring solution for connecting a 3-Wire RS-485 device to an ION Meter (COM1 or COM2).

NOTE: The fourth wire (Shield) should still be present in the communication wire bundle, but left unconnected at the ION meter.

Schneider Electric USA

How to connect 3-Wire Modbus to an ION Meter

The Shield and GND (ground) connections are internally connected in an ION meter using a diode bridge.
Wiring diagram

This is the best wiring solution for connecting a 3-Wire RS-485 device to an ION Meter (COM1 or COM2).

NOTE: The fourth wire (Shield) should still be present in the communication wire bundle, but left unconnected at the ION meter.

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.