How do I communicate with multiple ION 7600 over ethernet with DNP3.0?

Issue
DNP3.0 requires a unit ID even if it is over ethernet.

Product Line
ION 7500, ION7600

Environment
IONSetup

Cause
The framework in an ION7600 does not allow you to set the DLAddress for ethernet (which is essentially the unit ID).

Resolution

  1. Set COM2 to Ethergate
    Setup assistant
  2. Connect the twisted shielded pair (RS485) between COM1 and COM2
  3. Set the protocol on COM1 to DNP3.0 then set the unit ID to the desired number.
    Setup com protocol
NOTE: all devices and COM ports must have unique device IDs, and all operate at the same baud rate.

Schneider Electric USA

How do I communicate with multiple ION 7600 over ethernet with DNP3.0?

Issue
DNP3.0 requires a unit ID even if it is over ethernet. 

Product Line
ION 7500, ION7600

Environment
IONSetup

Cause
The framework in an ION7600 does not allow you to set the DLAddress for ethernet (which is essentially the unit ID).

Resolution

  1. Set COM2 to Ethergate
    Setup assistant
  2. Connect the twisted shielded pair (RS485) between COM1 and COM2
  3. Set the protocol on COM1 to DNP3.0 then set the unit ID to the desired number.
    Setup com protocol
NOTE: all devices and COM ports must have unique device IDs, and all operate at the same baud rate.

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.