What are the input circuit requirements for an EV Charging Station?
Issue:
What are the feeder circuit requirements for an EV Charging station?

Product Line:
PTEVC - ELECTRICAL VEHICLE

Resolution:
The EVlink series of Level 2 charging station require a 40A, non-GFI type breaker for each charging outlet.  #8 wire is required (L1, L2, and GND).  For dual outlet charging stations, two 40A non-GFI breakers will be required (one for each charging outlet).  A neutral connection is not required for EVlink stations.
A 40A circuit breaker is required as the continuous output current from the charging station can be as high as 30A.
The wiring diagram for a single outlet charging station is shown in the figure below.
EVlink Basic Wiring Diagram

Schneider Electric USA

What are the input circuit requirements for an EV Charging Station?
Issue:
What are the feeder circuit requirements for an EV Charging station?

Product Line:
PTEVC - ELECTRICAL VEHICLE

Resolution:
The EVlink series of Level 2 charging station require a 40A, non-GFI type breaker for each charging outlet.  #8 wire is required (L1, L2, and GND).  For dual outlet charging stations, two 40A non-GFI breakers will be required (one for each charging outlet).  A neutral connection is not required for EVlink stations.
A 40A circuit breaker is required as the continuous output current from the charging station can be as high as 30A. 
The wiring diagram for a single outlet charging station is shown in the figure below.
EVlink Basic Wiring Diagram

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.