How do I disable the Line Contactor on the E-Flex

Issue:
Customer wants to keep the line contactor in the circuit to allow the drive to decelerate verses freewheel stop.

Product Line:
E-Flex

Environment:
E-Flex with modification B09 (line contactor).
 
Cause:
The line contactor opens when the run command is removed.
 
Resolution:
There is no documentation / data to support this reconfiguration of the original design. This could possible have an effect on the drive ratings. Caution: This procedure should only be performed while power has been removed from the E-Flex.
Place a jumper between terminals 4 and 11.  This circuit modification will keep the line contactor closed when the switch is in the AFC position.  The line contactor will remain open when the switch is in OFF or BYPASS. 
 

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.