Issue:
Space required to add a PM 800 Series Power Meter into a NQ Panelboard enclosure. Can this be Field installed ?
Product Line:
NQ Panelboards and Powerlogic Power Meters
Environment:
Metering distribution
Cause:
Field installation
Resolution:
The NQ Panelboard enclosure needs extra inches of mounting space, and Metering can tonly be Factory installed .
The Factory installed PM800 Series meter will occupy an enclosure that will be extended 7" in Width and 6" in Height from the Factory.
BCPM , or Branch Circuit Power Metering can be used in NQ Panels ,and be field installed for individual metering of branch breaker loads., See attached Bulletin