undefined undefined
{}

Our Brands

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
What is the meaning of the B, C, D, K, and Z curves for C60 Multi-9 circuit breakers?

Issue:
What do the B curve, C curve, D curve, K curve and Z curve designations mean on Multi 9 breakers?

Product Line:
Circuit Breakers

Resolution:
For C60 Multi-9 devices, AC rated, the following is the meaning of the trip curves (in reference to instantaneous trip rating):
B curve: 3.2 - 4.8 times amp rating for UL489 and UL1077 (3 - 5 times amp rating for IEC)
C curve: 7 - 10 times amp rating
D curve: 10 - 14 times amp rating
K curve: 10 - 14 times amp rating
Z curve: 2.4 to 3.6 times amp rating

Schneider Electric USA

Attachment(s)
M9 Tripping Curves.pdf [457.49 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.