Where are the wiring diagrams for undervoltage trips (MN) and shunt trips (MX) for the PowerPacT breakers?
Product Line:
Circuit Breakers

Resolution:
There are two terminals on the UVR and the shunt trip accessories to which the control wires are attached (polarity does not matter).
  • The shunt trip will trip the circuit breaker if control voltage is applied across the two shunt trip terminals.
  • The undervoltage trip will trip the circuit breaker if control voltage is removed from the two undervoltage trip terminals.
Here are links to the instruction bulletins for the shunt trips and undervoltage trips of the PowerPacT breakers
PowerPacT H, J, and L document 48940-229-01
PowerPacT M, P, and R document 48049-245-03

Schneider Electric USA

Where are the wiring diagrams for undervoltage trips (MN) and shunt trips (MX) for the PowerPacT breakers?
Product Line:
Circuit Breakers

Resolution:
There are two terminals on the UVR and the shunt trip accessories to which the control wires are attached (polarity does not matter).
  • The shunt trip will trip the circuit breaker if control voltage is applied across the two shunt trip terminals.
  • The undervoltage trip will trip the circuit breaker if control voltage is removed from the two undervoltage trip terminals.
Here are links to the instruction bulletins for the shunt trips and undervoltage trips of the PowerPacT breakers
PowerPacT H, J, and L document 48940-229-01
PowerPacT M, P, and R document 48049-245-03

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.