Issue:
Main lug interior fitting into a larger than intended box
Product Line:
NQ Panleboards
Environment:
Retro fit
Cause:
Main breaker enclosure used with Main lug interior
Resolution:
Use the 12" rail and deadfront extension kit NQ12RDE to make up the 12" needed for the taller enclosure, when using a Main lug interior