How can we help you today?
Video: Resetting a LTMR Tesys T module back to factory default settings locally
Issue :
How to reset a LTMR Tesys T module back to factory default settings locally?
Product Line:
Motor control / Protection components
Environment:
LTMR
Tesys T
Cause:
Need to reset the module back to factory default settings locally to clear any user configuration.
Resolution:
1) Make sure the module is in one of the following states : Ready, Not ready or System configuration. (If the product is in Start or Run state, the return to factory setting is ignored)
2) Press and hold the Test/Reset button down for more than 15 seconds , but not exceeding 20 seconds and release it.
3) The unit will execute a reset to factory settings.
How to reset a LTMR Tesys T module back to factory default settings locally?
Product Line:
Motor control / Protection components
Environment:
LTMR
Tesys T
Cause:
Need to reset the module back to factory default settings locally to clear any user configuration.
Resolution:
1) Make sure the module is in one of the following states : Ready, Not ready or System configuration. (If the product is in Start or Run state, the return to factory setting is ignored)
2) Press and hold the Test/Reset button down for more than 15 seconds , but not exceeding 20 seconds and release it.
3) The unit will execute a reset to factory settings.
Released for:Schneider Electric USA
Explore more
Range:
Explore more
Range: