{}

Our Brands

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
Why does Vista crash when I try to start it? I don't even get to the login screen.
Issue:
I have done a Side-By-Side upgrade of a ION Enterprise 6.0 or earlier system to PME 7.2.x or PME 8.0. When I try to start Vista, I get a Windows dialog stating that 'Vista has stopped working.' with options to either 'Check online for a solution and close the program' or 'Close the Program'. I do see the splash screen, but I don't get as far as the login screen before Vista crashes.


Product Line:
Power Monitoring Expert 7.2.x
Power Monitoring Expert 8.0

Environment:
Power Monitoring Expert Software Upgrade

Cause:
This will happen if the config\cfg\ud directory includes a file called 'global.log' that was imported from your old system. The global.log file will be present if you have added a global event viewer. The newer version of Vista cannot process the old global.log file, as the old file format from ION Enterprise 6.0 or earlier is not compatible with PME 7.2.x or greater vista. Thus vista crashes.

Resolution:

*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).

Delete global.log from the Install Path\config\cfg\ud directory. Re-add a Global Event Viewer once Vista has started.

Schneider Electric USA

Why does Vista crash when I try to start it? I don't even get to the login screen.
Issue:
I have done a Side-By-Side upgrade of a ION Enterprise 6.0 or earlier system to PME 7.2.x or PME 8.0. When I try to start Vista, I get a Windows dialog stating that 'Vista has stopped working.' with options to either 'Check online for a solution and close the program' or 'Close the Program'. I do see the splash screen, but I don't get as far as the login screen before Vista crashes.


Product Line:
Power Monitoring Expert 7.2.x
Power Monitoring Expert 8.0

Environment:
Power Monitoring Expert Software Upgrade

Cause:
This will happen if the config\cfg\ud directory includes a file called 'global.log' that was imported from your old system. The global.log file will be present if you have added a global event viewer. The newer version of Vista cannot process the old global.log file, as the old file format from ION Enterprise 6.0 or earlier is not compatible with PME 7.2.x or greater vista. Thus vista crashes.

Resolution:

*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).

Delete global.log from the Install Path\config\cfg\ud directory. Re-add a Global Event Viewer once Vista has started.
 

Schneider Electric USA

Why does Vista crash when I try to start it? I don't even get to the login screen.
Issue:
I have done a Side-By-Side upgrade of a ION Enterprise 6.0 or earlier system to PME 7.2.x or PME 8.0. When I try to start Vista, I get a Windows dialog stating that 'Vista has stopped working.' with options to either 'Check online for a solution and close the program' or 'Close the Program'. I do see the splash screen, but I don't get as far as the login screen before Vista crashes.


Product Line:
Power Monitoring Expert 7.2.x
Power Monitoring Expert 8.0

Environment:
Power Monitoring Expert Software Upgrade

Cause:
This will happen if the config\cfg\ud directory includes a file called 'global.log' that was imported from your old system. The global.log file will be present if you have added a global event viewer. The newer version of Vista cannot process the old global.log file, as the old file format from ION Enterprise 6.0 or earlier is not compatible with PME 7.2.x or greater vista. Thus vista crashes.

Resolution:

*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).

Delete global.log from the Install Path\config\cfg\ud directory. Re-add a Global Event Viewer once Vista has started.
 

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
move-arrow-top
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.