What do the indication lights on the Micrologic trip units mean?

Issue:
Trip indicator lights on Micrologic

Product Line:
Circuit Breakers

Resolution:
Ir:
The Ir long-time pickup and delay levels were exceeded.
Isd/ Ii: The Isd short time pickup or the Ii instantaneous pickup was exceeded.
Ig: The Ig ground fault pickup level and delay levels were exceeded.
Ap: The self-protection indicator light lights when the trip unit causes the breaker to trip for a reason other than an overcurrent on the Ir, Ii, Isd, or Ig functions.
The Ap light can indicate:
* issue with internal current sensors, usually moisture or corrosion
* The instantaneous override level is exceeded
* fail-safe protection for the circuit in case of the trip unit malfunction
* trip unit temperature approaches 90°C
* overvoltage on 24 Vdc inputs F1-F2

Related Links
FA176046: Determining the cause of breaker tripping with Ap light indication on the Micrologic trip unit
Instruction Bulletin 48049-136-05:  Micrologic 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units


trip indication lights

Schneider Electric USA

What do the indication lights on the Micrologic trip units mean?

Issue:
Trip indicator lights on Micrologic

Product Line:
Circuit Breakers

Resolution:
Ir:   
The Ir long-time pickup and delay levels were exceeded.
Isd/ Ii:  The Isd short time pickup or the Ii instantaneous pickup was exceeded.
Ig:   The Ig ground fault pickup level and delay levels were exceeded.
Ap:   The self-protection indicator light lights when the trip unit causes the breaker to trip for a reason other than an overcurrent on the Ir, Ii, Isd, or Ig functions. 
The Ap light can indicate:
* issue with internal current sensors, usually moisture or corrosion
* The instantaneous override level is exceeded
* fail-safe protection for the circuit in case of the trip unit malfunction
* trip unit temperature approaches 90°C
* overvoltage on 24 Vdc inputs F1-F2

Related Links
FA176046: Determining the cause of breaker tripping with Ap light indication on the Micrologic trip unit
Instruction Bulletin 48049-136-05:  Micrologic 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units


trip indication lights
 

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.